- SECTION 07211
-
- SPRAYED FOAM INSULATION FOR BUILDING ENVELOPE
-
- NOTE ** Foam Enterprises sprayed polyurethane foam
- insulation for building envelope insulation.
- NOTE **
- NOTE ** This section is based on the products of Foam
- Enterprises, Inc., which is located at:
- NOTE ** 13630 Water Tower Circle
- NOTE ** Minneapolis, MN 55441
- NOTE ** Tel: (800) 888-3342
- NOTE ** Fax: (612) 559-0945
- NOTE **
- NOTE ** This section covers the foam insulation and vapor
- retarder, plus optional thermal barrier (fire
- resistive) coating or other material. This section
- should not be used for cold storage facility
- insulation -- use Section 07212 instead. For
- sprayed foam roofing, use Section 07570.
- NOTE **
- NOTE ** This specification is based on the following
- publication of the Society of the Plastics
- Industry, Inc., Spray Polyurethane Foam Division:
- NOTE **
- NOTE ** "Spray Polyurethane Foam Systems for Building
- Envelope Insulation and Air Seal; copyright 1994.
- NOTE **
- NOTE ** SECTION 07211 - SPRAYED FOAM INSULATION FOR
- BUILDING ENVELOPE, Copyright 1997, The Architect's
- Catalog, Inc.
-
- PART 1 GENERAL
-
- 1.1 SECTION INCLUDES
- NOTE ** Edit items below as required for project.
-
- A. Sprayed polyurethane foam insulation.
-
- B. Vapor retarder.
-
- C. Thermal barrier (fire resistive) coating.
-
- 1.2 RELATED SECTIONS
- NOTE ** Delete any sections below not relevant to this
- project; add others as required.
-
- A. Section 07260 - Vapor Retarders: Separate sheet vapor
- retarders.
- NOTE ** Roof Decks: This section should not be used to
- specify foam insulation on the exterior side of a
- roof -- use a true foam roofing specification for
- that.
-
- B. Section 07570 - Coated Foamed Roofing: Spray
- polyurethane foam on exterior side of roof decks.
-
- C. Section 09260 - Gypsum Board Assemblies: Gypsum board
- for thermal barrier covering foam insulation.
-
- D. Division 15 - Mechanical: Plumbing and HVAC components
- penetrating insulation.
-
- E. Division 16 - Electrical: Electrical components
- penetrating insulation.
-
- 1.3 REFERENCES
- NOTE ** Add any references to the list below that are
- included in text you have added to the section.
-
- A. ASTM D 1621 - Standard Test Method for Compressive
- Properties of Rigid Cellular Plastics.
-
- B. ASTM D 1622 - Standard Test Method for Apparent Density
- of Rigid Cellular Plastics.
-
- C. ASTM D 2856 - Standard Test Method for Open-Cell Content
- of Rigid Cellular Plastics by the Air Pycnometer.
-
- D. ASTM E 84 - Standard Test Method for Surface Burning
- Characteristics of Building Materials.
-
- E. ASTM E 96 - Standard Test Methods for Water Vapor
- Transmission of Materials.
-
- F. SPI Bulletin AX-119 - MDI-Based Polyurethane Foam
- Systems: Guidelines for Safe Handling and Disposal;
- Society of the Plastics Industry, Inc., Polyurethane
- Division.
-
- 1.4 SUBMITTALS
- NOTE ** Delete types of submittals not required.
- Coordinate submittal statements with other
- provisions in the section.
-
- A. Submit under provisions of Section 01300.
-
- B. Product Data: Manufacturer's data on products to be
- installed.
- 1. Application or installation instructions.
- 2. Listing, classification, and approval certifications.
- 3. Safety and handling instructions for storage,
- handling and use of the materials.
-
- C. Product Certification: SPI/SPDF accreditation test for
- materials.
-
- D. Certifications: If manufacturer's published data sheets
- do not indicate compliance with all specification
- requirements, provide letter of certification that all
- products comply with the specification requirements;
- include primers (if required), foam and coatings.
-
- E. Shop Drawings: Show materials and details of fabrication
- of sheet metal, accessories, or other fabricated items.
-
- F. Qualification Statements:
- 1. Manufacturer qualifications.
- 2. Installer qualifications.
- 3. Independent inspector qualifications.
-
- G. Applicator's Field Quality Control Procedures: Written
- description of procedures to be utilized to insure proper
- preparation and installation of foam and coatings, detail
- work and follow-up inspection.
-
- H. Maintenance Data: Manufacturers' recommended protection,
- cleaning, and repair procedures, including recommended
- frequency of inspection.
-
- 1.5 QUALITY ASSURANCE
-
- A. Installer Qualifications: A firm with experience
- installing insulation systems of the type specified.
- NOTE ** Delete the following paragraph if not required.
- NOTE **
- NOTE ** The Society of the Plastics Industry Spray
- Polyurethane Foam Division conducts an
- Accreditation Program for improvement of quality in
- the application of spray polyurethane foams and
- coatings.
- NOTE **
- NOTE ** The list of accredited individuals and firms is
- available from SPFD.
- 1. Show contractor/supplier level accreditation by SPI
- SPFD Accreditation Program.
- 2. Approved or certified by the foam manufacturer as
- qualified to install the specified system.
- 3. Provide information concerning projects similar in
- nature to the one proposed including location and
- person to be contacted.
-
- 1.6 DELIVERY, STORAGE, AND HANDLING
-
- A. Provide materials packaged in the manufacturer's
- original, tightly sealed containers or unopened packages,
- clearly labelled with the manufacturer's name, product
- identification, safety information, and batch or lot
- numbers where appropriate. Where materials are covered
- by a referenced specification, the labels shall bear the
- specification number, type and class, as applicable.
-
- B. Store materials out of the weather and out of direct
- sunlight in locations where the temperatures are within
- the limits specified by the manufacturer.
-
- 1.7 PROJECT CONDITIONS
- NOTE ** Normally safety procedures are the responsibility
- of the contractor. For more information about
- polyurethane foam see SPI Bulletin AX-119,
- "MDI-Based Polyurethane Foam Systems: Guidelines
- for Safe Handling and Disposal."
-
- A. Comply with the manufacturer's instructions and
- recommendations as to handling and safety procedures.
-
- PART 2 PRODUCTS
-
- 2.1 MANUFACTURERS
-
- A. Provide products of Foam Enterprises, Inc., 13630 Water
- Tower Circle, Minneapolis, MN 55441. ASD. Tel: (800) 888-
- 3342. Fax: (612) 559-0945.
-
- B. Substitutions are not acceptable.
- NOTE ** Delete paragraph above or below. Edit Section
- Number as required for project.
-
- C. Submit requests for substitutions in accordance with
- provisions of Section 01600.
-
- 2.2 MATERIALS
- NOTE ** Most published data is run on laboratory produced
- samples, not in-place material. The thickness of
- polyurethane foam sprayed, number of passes,
- temperature of substrate, ambient temperatures,
- etc., all affect properties. The following values
- are for Foam Enterprises' product in-place.
-
- A. Foam: Sprayed-in-place two-component closed-cell
- polyurethane made by combining an isocyanate (A)
- component with a polyol (B) component, with the following
- physical characteristics:
- 1. Density in place, when tested in accordance with ASTM
- D 1622: 1.7 to 1.8 lb/cu ft (27 to 29 kg/cu m).
- 2. Compressive Strength, when tested in accordance with
- ASTM D 1621: 20 to 30 psi (1.4 to 2.1 Pa), minimum.
- 3. Closed Cell Content, when tested in accordance with
- ASTM D 2856: 87 percent, minimum.
- 4. R-value, aged: 6.8.
- NOTE ** From a fire safety standpoint, polyurethane foams
- can be used safely. It is important, however, that
- all persons associated with the design,
- fabrication, storage and installation understand
- the materials and environments involved.
- NOTE **
- NOTE ** Polyurethane foam insulation is combustible and
- should be treated as such. Flame spread ratings
- provided for polyurethane products using small
- scale tests are not intended to reflect the hazards
- presented by this or any other materials under
- actual fire conditions. Care must be taken to
- ensure that the foam is not exposed to heat or
- flame.
- 5. Flame Spread Index, when tested in accordance with
- ASTM E 84: Less than 75.
- 6. Smoke Developed Index, when tested in accordance with
- ASTM E 84: Less than 450.
-
- B. Primers: As recommended by the manufacturer of the spray
- foam materials specified.
- NOTE ** The following paragraph is for a vapor retarder
- coating to be applied directly to the foam. If the
- foam is to be covered by other construction, such
- as gypsum drywall, other types of vapor barriers
- can be used -- specify them in another section.
-
- C. Vapor Retarder: Fluid-applied coating, Lion Oil Co.,
- Nokorde 706M; permeability of 0.01 perm or less, when
- tested in accordance with ASTM E 96, Method D.
- NOTE ** A thermal barrier (fire resistive) is almost always
- required over polyurethane foam exposed on the
- interior of the building. Typically, the minimum
- thermal barrier is a material that constitutes 15
- minutes of fire protection for the foam. Materials
- that have been used include sprayed cementitious or
- fiber material (such as fireproofing) and gypsum
- board.
- NOTE **
- NOTE ** Delete the following paragraph if the thermal
- barrier is not a coating and is specified in
- another section.
-
- D. Thermal Barrier: Sprayed coating, W.R. Grace Zonolite
- 3306 or International Cellulose Ure-K; applied for fire
- resistance rating of 15 minutes.
-
- PART 3 EXECUTION
-
- 3.1 GENERAL
-
- A. Comply with the instructions and recommendations of the
- foam and coatings manufacturers.
-
- B. Familiarize all installers with correct and safe
- application and handling procedures:
- 1. See SPI Bulletin AX-119, "MDI-Based Polyurethane Foam
- Systems: Guidelines for Safe Handling and Disposal."
- 2. Refer to appropriate Materials Safety Data Sheets
- (MSDS) for additional safety information.
-
- 3.2 PREPARATION
-
- A. Primed Steel: If the surface is free of loose scale,
- rust, weathered or chalking paint, it can be cleaned
- using vacuum equipment and hand or power tools to remove
- loose dirt.
-
- B. Previously Painted Steel: Clean using hand or power
- tools to remove loose scale and dirt.
-
- C. Galvanized Steel and Unpainted Steel: Clean as
- recommended by primer manufacturer.
-
- D. New Concrete: Allow to cure for twenty-eight (28) days
- prior to the application of primer or foam.
-
- E. Previously Painted Surfaces: Remove all loose paint.
-
- F. Remove loose dirt, dust and debris by using compressed
- air, vacuum equipment or brooming. Remove oil, grease,
- form release agents, laitance, and other contaminants
- using proper cleaning solutions. Do not wash wood or
- porous materials with water.
-
- G. Grout, tape, or calk all joint openings that exceed 1/4
- inch (6 mm) in width.
-
- H. Prime all metal as recommended by manufacturer.
-
- I. Prime all concrete surfaces.
-
- 3.3 FOAM APPLICATION
-
- A. Do not begin application of foam until all preparation
- requirements have been completed.
-
- B. Do not apply foam when the temperature is below or the
- humidity is above that specified by the manufacturer for
- ambient air and substrate.
-
- C. Apply foam in accordance with the manufacturer's
- specifications and instructions.
-
- D. Apply foam to a ____ inch (____ mm) thickness, with pass
- thickness of 1/2 inch (13 mm) to 1-1/2 inches (38 mm).
- Complete the full thickness of foam in any area prior to
- the end of each day.
- NOTE ** The following article is for vapor retarder
- coating. Delete if a sheet-type vapor retarder is
- used.
-
- 3.4 VAPOR RETARDER INSTALLATION
-
- A. Apply vapor retarder in accordance with building code
- requirements and the manufacturer's specifications and
- instructions.
-
- B. Apply vapor retarder to the entire surface of the foam in
- a continuous film across corners and junctions.
- NOTE ** Delete the following article if the thermal barrier
- is not a spray-applied coating.
-
- 3.5 THERMAL BARRIER APPLICATION
-
- A. Allow vapor retarder to cure before the thermal barrier
- coating is applied. Repair damage and defects to the
- vapor retarder prior to the application of the thermal
- barrier.
-
- B. Apply thermal barrier over entire surface of foam.
-
- C. Allow thermal barrier to cure. Inspect for defects and
- repair defects prior to subsequent coats.
-
- END OF SECTION
-